Toyota Camry
XV30 (2002–2006) Service Manual
Heater & air conditioner
Refrigerant
ON−VEHICLE INSPECTION
1. INSPECT REFRIGERANT VOLUME
a. Observe the sight glass on the cooler refrigerant liquid
pipe A.
Test conditions:
- Running engine at 1,500 rpm
- Blower speed control switch at ”HI”
- A/C switch ON
- Temperature control dial at ”MAX. COOL”
- Fully open the doors
Item |
Symptom |
Amount of refrigerant |
Corrective Actions |
1 |
Bubbles present |
Insufficient* |
- Check for gas leakage and repair if necessary
- Add refrigerant until bubbles disappear
|
2 |
No bubbles present |
None, insufficient or too much |
Refer 3 and 4 |
3 |
No temperature difference between compressor
inlet and outlet |
Empty or nearly empty |
- Check for gas leakage with gas leak detector
and repair if necessary
- Add refrigerant until bubbles disappear
|
4 |
Considerable temperature difference between
compressor inlet and outlet. |
Correct or too much |
Refer to 5 and 6 |
5 |
Immediately after air conditioning is turned
off, refrigerant clear |
Too much |
- Discharge refrigerant
- Remove air and supply proper amount or
purified refrigerant
|
6 |
Immediately after air conditioning is turned
off, refrigerant foams and then becomes
clear |
Correct |
− |
*: Bubbles in the sight glass with ambient temperatures higher than usual can
be considered normal if cooling
is sufficient.
2. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD
GAUGE SET
a. This is a method in witch the trouble is located by using
a manifold gauge set. Read the manifold gauge pressure
when the these conditions are established.
Test conditions:
- Temperature at the air inlet with the switch set
at RECIRC is 30 − 35 °C (86 − 95 °F)
- Engine running at 1,500 rpm
- Blower speed control switch at ”HI” position
- Temperature control dial at ”COOL” position
- A/C switch ON
- Fully open doors
1. Normally functioning refrigeration system.
Gauge reading:
Low pressure side:
0.15 − 0.25 MPa (1.5 − 2.5 kgf/cm2)
High pressure side:
1.37 − 1.57 MPa (14 − 16 kgf/cm2)
2. Moisture present in refrigeration system.
Symptom |
Probable cause |
Diagnosis |
Remedy |
During operation, pressure on low
pressure side sometimes become
a vacuum and sometime normal |
Moisture in refrigerating system
freezes at expansion valve orifice
causing a temporary stop of cycle,
however, when it melts, normal
state is restored. |
- Drier in oversaturected state
- Moisture in refrigerating system
freezes at expansion valve orifice
and blocks circulation of refrigerant
|
- Replace condenser
- Remove moisture in cycle by
repeatedly evacuating air
- Supply proper amount of new
refrigerant
|
3. Insufficient coolin
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
- Pressure low on both low and
high pressure sides
- Bubbles seen thought sight glass
continuously
- Insufficient cooling performance
|
Gas leakage in refrigeration system |
- Insufficient refrigerant
- Refrigerant leaking
|
- Check for gas leakage and repair
if necessary
- Supply proper amount of new
refrigerant
- If indicated pressure value is
close to a 0 when connected to
gauge, create the vacuum after inspecting
and repairing location of
leak
|
4. Poor circulation of refrigerant
Symptom |
Probable cause |
Diagnosis |
Corrective Action |
- Pressure low on both low and
high pressure sides
- Frost on pipe from condenser to
unit
|
Refrigerant flow obstructed by dirt
in receiver |
Receiver clogged |
Replace condenser |
5. Refrigerant does not circulate
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
- Vacuum indicated on low pressure
side, very low pressure indicated
on high pressure side
- Frost or dew seen on piping before
and after receiver/ drier or expansion
valve
|
- Refrigerant flow obstructed by
moisture or dirt in refrigerating system
- Refrigerant flow obstructed by
gas leaked from expansion valve
|
Refrigerant does not circulate |
- Check expansion valve
- Clean out dirt in expansion
valve by air blowing
- Replace condenser
- Evaporate air and supply proper
amount of new refrigerant.
- For gas leakage from expansion
valve, replace expansion
valve
|
6. Refrigerant overcharged or insufficient cooling of
conden
Symptom |
Probable cause |
Diagnosis |
Remedy |
- Pressure too high on both low
and high pressure sides
- No sir bubbles seen through the
sight glass even when the engine
rpm is lowered
|
- Unable to develop sufficient performance
due to excessive use of
refrigerating system
- Insufficient cooling of condenser
|
- Excessive refrigerant in
cycle"too much refrigerant supplied
- Condenser cooling
insufficient"condenser fins
clogged at cooling fan
|
- Clean condenser
- Check cooling fan with cooling
fan motor operation
- If 1. and 2. are in normal
state, check amount of refrigerant
and supply proper amount of refrigerant
|
7. Air present in refrigeration system
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
- Pressure too high on both low
and high pressure sides
- The low pressure piping too hot
to the touch
- Bubbles seen through sight glass
|
Air entered in refrigerating system |
- Air present in refrigerating system
- Insufficient vacuum purging
|
- Check compressor oil to see if
it is see if it is dirty or insufficient
- Evacuate air and supply new
refrigerant
|
8. Expansion valve improperly
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
- Pressure too high on both low
and high pressure sides
- Frost or large amount of dew on
piping on low pressure side
|
Trouble in expansion valve |
- Excessive refrigerant in low
pressure piping
- Expansion valve opened too
wide
|
Check expansion valve |
9. Defective compression compressor
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
- Pressure too high on low high
pressure sides
- Pressure too low to on high pressure
side
|
Internal leak in compressor |
- Compression failure
- Leakage from valve damaged or
broken sliding parts
|
Repair or replace compressor |
Gauge readings (Reference)
More about «Heater & air conditioner»:
Refrigerant